Sensor#
( Circuit Element, Meter Element )
# |
Name |
Type |
Default |
Units |
Description |
---|---|---|---|---|---|
1 |
|
string |
Name (Full Object name) of element to which the Sensor is connected. |
||
2 |
|
integer |
1 |
Number of the terminal of the circuit element to which the Sensor is connected. 1 or 2, typically. |
|
3 |
|
real |
12.47 |
kV |
Voltage base for the sensor, in kV. If connected to a 2- or 3-phase terminal, |
4 |
|
boolean |
False |
Clear=Yes clears sensor values. Should be issued before putting in a new set of measurements. |
|
5 |
|
array of reals |
Array of Voltages (kV) measured by the voltage sensor. For Delta-connected sensors, Line-Line voltages are expected. For Wye, Line-Neutral are expected. |
||
6 |
|
array of reals |
Array of Currents (amps) measured by the current sensor. Specify this or power quantities; not both. |
||
7 |
|
array of reals |
Array of Active power (kW) measurements at the sensor. Is converted into Currents along with q=[…] |
||
8 |
|
array of reals |
Array of Reactive power (kvar) measurements at the sensor. Is converted into Currents along with p=[…] |
||
9 |
|
string |
Wye |
Voltage sensor connection. Applies to voltage measurement only. |
|
10 |
|
integer |
1 |
Default is 1: 1-2, 2-3, 3-1. For reverse rotation, enter -1. |
|
11 |
|
real |
Assumed percent error in the measurement. |
||
12 |
|
real |
1.0 |
Weighting factor. |
|
13 |
|
real |
Hz |
Base Frequency for ratings. |
|
14 |
|
boolean |
True |
Indicates whether this element is enabled. |
|
15 |
|
string |
Make like another object, e.g.: |